Fiyuusyada Isku-dhafka ah ee Dabdemiska Vacuum Load
Qaabka iyo Macnaha
Xaalada Ambient
heerkulka deegaanka: Max.heerkulka+40 ℃;Min.heerkulka-15 ℃
Qoyaanka deegaanka: qoyaan qaraabo ah maalintii ≤ 95%;Qoyaan qaraabo ah bishii ≤ 90
Dhererka goobta uu adeegga Switch uu gaari karo 1000m
Xaalad adeeg gaar ah, fadlan la xiriir soo saaraha
Heerka Tixraaca
GB3804-2004 Badalka Voltage-sare ee beddelka-hadda ee danab la qiimeeyay oo ka sarreeya 3.6kV iyo ilaa iyo ay ku jiraan 40.5kV
GB16926-2009 Voltage-sare beddelka-fiyuuska beddelka hadda
GB/T11022-1999 Tilmaamaha guud ee qalabka korantada sare iyo heerarka kontoroolka
Halbeegyada Farsamo ee ugu muhiimsan ee beddelka
Magaca | Unug | Bedel GPL-24/T630-20 | Isku-darka fiyuuska GPLR-24/T125-40 | |
danab la qiimeeyay | kV | 24 | 24 | |
Inta jeer ee la qiimeeyay | Hz | 50 | 50 | |
Hadda la qiimeeyay | A | 630 | 125 (sida fiyuuska) | |
Lagu qiimeeyay Dahaarka heerka | 1min inta jeer ee korontadu waxay u adkeysan kartaa danab | kV | Xidhiidhada ka dambeeya ee jabiyayaal furan 65; Marxaladda wejiga, wejiga ilaa dhulka 65 | |
Dareenka iftiinka u adkaysta danab | kV | Marxaladda wejiga, wejiga ilaa dhulka 125; Xidhiidhada ka joojinta ee go'doominta ayaa furan 125 | ||
La qiimeeyay hadda jebinta wareegga gaaban | kA | - | 40 | |
Xamuulka firfircoon ee jabinaya hadda | A | 630 | - | |
Lagu qiimeeyay xiritaanka wareegga jabinta hadda | A | 630 | - | |
Culays firfircooni jaban oo hooseeya | A | 31.5 | - | |
Fiilada la qiimeeyay ee jabinta hadda | A | 16 | 16 | |
Wareeg gaaban oo la qiimeeyay samaynta hadda (ugu sarreysa) | kA | 50 | 100 | |
Lagu qiimeeyay waqti gaaban oo u adkaysan kara hadda | kA | 20 | - | |
Waqtiga gaaban ee la qiimeeyay ayaa u adkeysanaya muddada hadda jirta | S | 4 | - | |
Heerka ugu sarreeya ee u adkeysiga hadda jira | kA | 50 | - | |
La-wareejinta hadda | A | - | 3150 | |
Iska caabinta wareegga | μΩ | ≤150 | ≤250+ Fuse | |
Awoodda matoorka | W | 90 | ||
Dhaqdhaqaaqa iyo xidhiidhka go'an ee la oggol yahay dhumucda ururinta naaxinta | mm | 3 | ||
Nadiifinta xiriiryada furan | mm | 12±1 | ||
Waqtiga xidhidhiyaha xidhidhiyaha | ms | ≤2 | ||
3-fase asynchronous | ms | ≤2 | ||
Celceliska xawaaraha xidhitaanka | m/s | 0.8±0.2 | ||
Celceliska xawaaraha furitaanka | m/s | 1.3 ± 0.2 | ||
adkaysiga makaanikada | Waqtiyada | 10000 |
Halbeegyada Farsamo ee ugu Muhiimsan ee Matoorka
Magaca | Unug | Halbeegyada |
danab hawlgalka lagu qiimeeyay | V | AC/DC 110/220 |
galinta awooda la qiimeeyay | W | 80 |
Kala duwanaanshaha tamarta caadiga ah ee matoorka |
| 85% ~ 110% danab hawlgalka lagu qiimeeyay |
Waqtiga dallacaadda | s | ≤15 |
Farsamada ugu weyn ee Gariiradda
Magaca | Unug | Halbeegyada | |
danab hawlgalka lagu qiimeeyay | V | AC, DC110 | AC, DC220 |
Hawlgalka hadda la qiimeeyay | A | ≤3 | ≤2 |
Kala duwanaanshaha tamarta caadiga ah ee gariiradda dhow |
| 85% ~ 110% danab hawlgalka lagu qiimeeyay | |
Kala duwanaanshaha korantada caadiga ah ee gariiradda safarka |
| 65% ~ 120% danab hawlgalka lagu qiimeeyay |
Qaab dhismeedka iyo shaqada
Gawaarida nooca GPL(R) waxay ka kooban tahay habka hawlgalka iyo qolalka arc-daminta ee habka dambeedka hore, wareeggiisa ugu muhiimsan ee qaab-dhismeedka sagxadda.Qolka vacuum arc-deminta waxaa lagu hagaajiyaa qaab dhismeedka dahaarka toosan ee cannular ka samaysan ee epoxy resin by technology APG, sidaas darteed leh aad u wanaagsan anti-creepage Qaab dhismeedka noocan oo kale ah design weyn taas oo yaraynaysaa raasamaal ee boodhka dusha sare ee vacuum arc-deminta qolka, ma aha oo kaliya inay ka hortagto qolka daminta faakuumka saamaynta dibadda, laakiin sidoo kale waxay xaqiijin kartaa inay soo bandhigto xaalad iska caabin sare leh oo ka dhan ah saameynta danab xitaa cimilada diiran-qoyan ama jawi wasakhaysan oo culus.
Habka hawlgalka guga ee lagu habeeyay qashin-qubka diyaaradda waxa lagu dallaci karaa buug-gacmeedka ama matoorka, habka hawlgalka ee ku yaal sanduuqa birta ee ku yaal dhinaca hore ee qolka dab-demiska.Sanduuqa waxa loo qaybiyaa shan meel oo isku imaatin ah oo loo qaybiyo afar saleebaan, meeshan waxa ku yaala qayb dallad, qayb quusin, qayb sii dayn ah iyo qalab si gaar ah u ilaalinaya.Qaab dhismeedka GPL(R) nooca beddelka kaas oo habka hawlgalka iyo qolalka arc-daminta loo habeeyey qaab isku dhafan oo gadaal-dambe ah ayaa si fiican u waafajin kara waxqabadka hawlgalka ee habka hawlgalka iyo waxqabadka loo baahan yahay jebinta iyo samaynta qolka arc-daminta.Sidoo kale, waxay yarayn kartaa ereyada badhtamaha ee aan loo baahnayn oo waxay yaraynaysaa qaylada iyo tamarta la isticmaalo si ay u hogaamiso waxqabadka GPL(R) oo la isku halayn karo.