Qalabka la isku daray ee Vacuum Contactor Switch Fiyuuska
Xaalada Ambient
1) Heerkulka deegaanka: -25℃~+45℃, celceliska maalinlaha ah: ≤35℃
2) Joog: 1000m (Standard);waxay gaari kartaa ilaa 4500m dalbashada gaarka ah;
3) Qoyaanka qaraabada: celceliska maalinlaha ah ≤95%, celceliska bishii ≤90%;
4) Xoogga dhulgariirka ≤8 darajo;
5) Munaasabadaha lagu dabaqi karo waa in ay ka xoroobaan waxyaabaha gubanaya, walxaha qarxa, daxalka iyo gariirka daran.
Halbeegyada Farsamo ee Muhiimka ah ee Qalabka Isku-dhafka ah ee Xiriiriyaha-Fiyuuska Vacuum ee Gpvc
Walxaha | Unug | Xogta | |||
Voltage lagu qiimeeyay | kV | 3.6 | 7.2 | 12 | |
1min inta jeer ee korontadu waxay u adkeysan kartaa danab | kV | 20 | 32 | 42 | |
Dareenka iftiinka ayaa u adkeysanaya danabka | kV | 46 | 60 | 75 | |
Hadda la qiimeeyay | A | 400 | 315 | 200 | |
Lagu qiimeeyay adkaysiga wakhtiga gaaban (4s) | kA | 4 | |||
Heerka ugu sarreeya ee u adkeysiga hadda jira | kA | 10 | |||
Dabacsanaanta wareegga gaaban ee la filayo | kA | 50 | |||
Xilliga dhow ee wareegga gaaban ee la filayo | kA | 130 | |||
Iska caabinta wareegga ugu weyn | uΩ | ≤250+RFuse | |||
Max.wareejinta hadda | A | 4000 | 4000 | 3200 | |
La qiimeeyay waqtiyada jebinta hadda | waqtiyo | 250,000 | |||
Nolosha makaanikada | Nooca qabsashada makaanikada | waqtiyo | 300,000 | ||
Nooca koronto-qabsiga | waqtiyo | 500,000 | |||
Iska caabinta wareegga ugu weyn | uΩ | ≤150 |
Qorshaha Gpvc Vacuum Contactor-Fiyuuska Isku-dhafka
Lambarka qorshaha | Qorshaha -1 | Qorshaha - 2 | |
Qorshaha aasaasiga ah | |||
| Hadda la qiimeeyay (A) | ~400 | ~400 |
Ugu weyn qaybaha | Vacuum contactor-Fuse isku darka - GPVC | 1 | 1 |
Transformer hadda LZZBJ | 3 | 3 | |
Transformer Voltage JDZ10 ama JDZX10 |
|
| |
Fiyuuska tamarta sare ee XRNM-10 | 3 | 3 | |
Dhul-bedelka GPJN15-12 |
| 1 | |
Qalabka kormeeraha korantada | Sida looga baahan yahay Isticmaalayaasha | Sida looga baahan yahay Isticmaalayaasha | |
Hadallo | Baabuurka wadista | Baabuurka wadista |