Qiyaasta Farsamada
Maya | Walxaha | Unug | Xogta | |||
1 | danab la qiimeeyay | kV | 40.5 | |||
2 | Inta jeer ee la qiimeeyay | Hz | 50 | |||
3 | 1min inta jeer ee korontadu waxay u adkeysan kartaa danab | Ulaha dhexdooda, Dhulka | kV | 95 | ||
Jabka | 118 | |||||
Hilaaca adkaysi danab | Ulaha dhexdooda, Dhulka | 185 | ||||
Jabka | 215 | |||||
4 | Hadda la qiimeeyay | A | 1250 1600 2000 2500 | |||
5 | Lagu qiimeeyay adkaysiga wakhtiga gaaban (RMS) | kA | 25 | 31.5 | ||
6 | Heerka ugu sarreeya ee u adkeysiga hadda jira | 63 | 80 | |||
7 | La qiimeeyay jabinta hadda jirta ee wareegga gaaban (RMS) | 25 | 31.5 | |||
8 | La qiimeeyay samaynta wareega gaaban ee hadda (qiimaha ugu sarreeya) | 63 | 80 | |||
9 | Lagu qiimeeyay muddada wareegga gaaban | s | 4 | |||
10 | Isku xigxiga hawlgallada | O-0.3s-CO-180s-CO | ||||
11 | Waxaa lagu qiimeeyay khaldaadka dhulka ee ka baxsan wajiga | kA | 21.7 | 27.4 | ||
12 | Tijaabada wareejinta fiilada ee la qiimeeyay | A | 50 | |||
13 | La qiimeeyay hal/dib-u-dhac capacitor bangi jabinaya hadda | 800/800 | ||||
14 | Nolosha makaanikada | waqtiyo | 10000 | |||
15 | Waqtiyada jabinta wareegga gaaban ee hadda jira | waqtiyo | 30 | |||
16 | Wareegga labaad 1 daqiiqo inta jeer ee awooda u adkeysaneyso danab | 2000 | ||||
17 | Danab shaqaynaysa oo la qiimeeyay | Xiritaanka gariiradda | V | DC110/220, AC220 | ||
Gariiradda furitaanka | V | DC110/220, AC220 | ||||
18 | danab lagu qiimeeyay matoorka kaydinta tamarta | W | DC110/220, AC220 | |||
19 | Awoodda la qiimeeyay ee matoorka kaydinta tamarta | s | 250 | |||
20 | Waqtiga kaydinta tamarta (korontada la qiimeeyay) | s | ≤10 | |||
21 | Cadaadis lagu qiimeeyay gaaska SF6 (cadaadiska cabbirka 20°C) | Mpa | 0.350+0.02 | |||
22 | Cadaadiska digniinta | Mpa | 0.29±0.01 | |||
23 | Cadaadiska shaqada ee ugu yar (cadaadiska xannibista) | Mpa | 0.28±0.01 | |||
24 | Heerka daadinta sannadlaha ah | % | ≤0.5 | |||
25 | Qoyaanka gaasta | μL/L | ≤150 | |||
26 | Dhaqdhaqaaqa istaroogga xidhiidhka | mm | ≥78 | |||
27 | Kala fogeynta xiriirka | mm | 50± 1.5 | |||
28 | Waqtiga furitaanka | ms | 60 ~ 78 | |||
29 | Waqtiga xidhitaanka | ms | 65 ~ 95 | |||
30 | Xiritaanka iyo furitaanka saddex-waji ma aha xilliyo | ≤5 | ||||
31 | Celceliska xawaaraha furitaanka (10ms gudahood ka dib kala badh) | ms | 2.2 ~ 2.8 | |||
32 | Celceliska xawaaraha xidhitaanka (gudahood 10ms badhkii ka dib) | ms | ≥1.5 | |||
33 | Iska caabbinta wareegga ugu weyn | μΩ | ≤32 (Gacan-gacmeed) | ≤20 (nooc go'an) |